PanelView 1000
The PanelView 1000 product series was designed by Allen-Bradley/Rockwell Automation to provide an effective industrial control solution. It is the follow-up to PanelView 300, 550, and 600 series. Unlike the PanelView 300, 550, and 600 series, the PanelView 1000 series provides a lot of new features and user options.
Product Features
- It is an IEC/EN 61131-2 equipment, Class I device.
- It has a colored or grayscale display.
- It has a 10-inch-wide LCD.
- It provides the user with both touch and keypad input.
- It is embedded with Active-matrix thin film transistor or TFT display type.
- It has a resolution of 640 x 480 pixels.
- It has 16 keys for input and functions.
- This product may be used in non-hazardous environments.
- In the case of a hazardous environment, PanelView 1000 terminals may be mounted inside an enclosure.
- It has multiple communications ports that can help establish links between either single or multiple controllers.
- A memory card slot is available.
- A memory card retainer is present on PanelView 1000 terminals. This encloses the memory card and saves it from dropping out of the terminal when it is vibrating.
Catalog Number
The catalog number for PanelView 1000 terminals include:
- 2711-K10Gxx: This is the catalog number for a PanelView 1000 terminal with a grayscale display and a keypad input.
- 2711-K10Cxx: This is the catalog number for a PanelView 1000 terminal with a colored display and a keypad.
- 2711-T10Gxx: This is the catalog number for a PanelView 1000 terminal with a grayscale display and a touchscreen.
- 2711-T10Cxx: This is the catalog number for a PanelView 1000 terminal with a colored display and a touchscreen.
Dimensions
If the user has selected a PanelView 1000 terminal with a touchscreen, then the dimensions measure 370 mm x 282 mm x 112 mm (14.58 in x 11.11 in x 4.40 in).
If the user has selected a PanelView 1000 terminal with a keypad, then the dimensions measure 473 mm x 282 mm x 112 mm (16.64 in x 11.11 in x 4.40 in).
Clearance
If the user is mounting a PanelView 1000 terminal in an enclosure, certain clearances within the enclosure must be ensured by the user before using the device. These clearances are as follows:
- 51 mm at both sides for airflow.
- 51 mm at the top and bottom for mounting and wiring connections.
- 222 mm of clearance is required for memory cards and the memory card retainer.
These clearances are done for the following purposes:
- Maintaining the temperature and airflow inside the enclosure.
- Maintenance of a PanelView 1000 terminal.
- Provision of enough space for the wiring.
- Memory card slot access and memory card retainer access.
- Memory card insertion and removal.
Enclosure
If a PanelView 1000 terminal is chosen, the user must ensure the provision of a working environment with EN/IEC 61131-2 pollution degree 2 protection, otherwise, there is a possibility that the product may malfunction. For installation in hazardous environments, PanelView 1000 terminals can be mounted inside a panel or an enclosure. In that case, the panel or the enclosure should meet the NEMA Type 12/13 rating. This must be ensured to protect the internal circuitry. The ambient temperature inside the panel or the enclosure must range from 0 to 55 degrees Celsius. The user also must ensure access to the back panel and slots of a PanelView 1000 terminal for wiring, troubleshooting, maintenance, installation of a memory card, and so on.
Hazardous Environment Considerations
There are specified classes with distinctive divisions and groups that define the locations where a PanelView 1000 terminal can operate safely. These include:
- Class I, Division 2: Groups A, B, C, and D.
- Class II, Division 2: Groups F and G.
- Class III or non-hazardous locations.
Users must refer to these details to select their PanelView 1000 terminal. One important aspect to consider is that all other versions of PanelView terminals, including the PanelView 300, PanelView 550, PanelView 600, PanelView 700, and PanelView 900, operate under the same category of class, division, and groups as PanelView 1000 terminals do. Users must ensure that the class, division, and group classifications are considered for PanelView 1000 terminals. There are separate instructions for installation in a hazardous environment, which include:
- Installing the terminal in an enclosure.
- All the connection cables and wiring are to be contained inside the enclosure.
- Wiring within the enclosure must be done as per the instructions of the National Electric Code.
- Avoid replacing and disconnecting equipment and components when the power is active.
Power Specifications
The power specifications for both PanelView 1000G and PanelView 1000C terminals are given below:
AC Power:
In the case of an AC power source:
- The supply voltage for both PanelView 1000G and PanelView 1000C terminals ranges from 85 to 264V AC at an operating frequency ranging from 47 to 63 Hz.
- The maximum power consumption for both PanelView 1000G and PanelView 1000C terminals is 55 volt-amperes or 55 watts.
DC Power:
The PanelView 1000 terminals with catalog numbers ending with L1 (For example 2711-T10G1L1) usually operate on DC power. In the case of a DC power source:
- The supply voltage for both PanelView 1000G and PanelView 1000C terminals is 8 to 32V DC.
- The nominal DC voltage for both PanelView 1000G and PanelView 1000C terminals is 24 V.
- The maximum power consumption for both PanelView 1000G and PanelView 1000C terminals is 24 watts.
Other Specifications
- The weight of PanelView 1000G and PanelView 1000C terminals with a touch screen is 3 kilograms (6.6 pounds).
- The weight of PanelView 1000G and PanelView 1000C terminals with a keypad is 3.06 kilograms (6.7 pounds).
- The dimensions for PanelView 1000G and PanelView 1000C terminals with a keypad are 282 mm × 423 mm × 112 mm.
- The dimensions for PanelView 1000G and PanelView 1000C terminals with a touch screen are 282 mm × 370 mm × 112 mm.
- The flash memory for PanelView 1000G and PanelView 1000C terminals is 1008 kilobytes.
- The display type used in both PanelView 1000G and PanelView 1000C terminals are classified as Active-matrix thin film transistors with a Cold Cathode Fluorescent Backlight.
- The display screen size for both PanelView 1000G and PanelView 1000C terminals is 211 mm × 158 mm (8.3 in × 6.2 in).
- The total number of touch cells for both PanelView 1000G and PanelView 1000C terminals is 384.
- The touch cell size for both PanelView 1000G and PanelView 1000C terminals is 26 × 30 pixels.
Communication Port
The PanelView 1000 terminal supports multiple communication types including DH+, ControlNet, Ethernet, Remote I/O, DeviceNet, etc. Each communication type is integrated with PanelView 1000 in a different configuration with different communication rates. The communication rates for different communication types are given below:
-
Communication Type: DH-485
- Communication Rate: 1.2 k, 2.4 k, 9.6 k, 19.2 k
- Max Distance: 1219 m
-
Communication Type: DH+
- Communication Rate: 57.6 k, 155.2 k, 230.4 k
- Max Distance: 3048 m
-
Communication Type: RS-232
- Communication Rate: 1.2 k, 2.4 k, 9.6 k, 19.2 k
- Max Distance: 6.1 m
-
Communication Type: Remote I/O
- Communication Rate: 57.6 k, 115.2 k
- Max Distance: 2800 m, 1400 m
-
Communication Type: DeviceNet
- Communication Rate: 125 k, 250 k, 500 k
-
Communication Type: ControlNet
- Communication Rate: 5 M
- Max Distance: 1000 m
-
Communication Type: Ethernet
- Max Distance: 100 m
-
Communication Type: DF1
- Max Distance: 15.24 m
DeviceNet Communication:
The PanelView 1000 terminals with DeviceNet ports usually have 10 at the end of their catalog number. The DeviceNet terminals of the PanelView 1000 series can connect at the device level on a DeviceNet link. It can connect with PLC-5, SLC 500, and ControlLogix. If the user wants to connect to a PLC, SLC, or ControlLogix controller to the DeviceNet link, a DeviceNet scanner module must be used.
To connect the PanelView 1000 DeviceNet port with the DeviceNet network, users may select any of the cables below according to their system requirements:
- 50-meter DeviceNet cable
- 100-meter DeviceNet cable
- 150-meter DeviceNet cable
ControlNet Communication:
PanelView 1000 terminals provide users with the option of ControlNet communications. Usually, PanelView 1000 terminals come with a ControlNet terminal that can connect with single or multiple controllers on a ControlNet network. The controllers compatible with ControlNet include:
- ControlLogix; connected using 1756-CNB
- PLC-5/20C
- PLC-5/40C
- PLC-5/60C
- PLC-5/80C
Users can select the ControlNet terminal as it supports unscheduled and scheduled access to controller data, along with redundant cabling.
Data Highway Plus Communication:
The PanelView terminals with DH+ terminals have 8 at the end of their catalog number. Users may select the DH+ communication terminals if they want to achieve either direct communication with a single controller or network communication with multiple controllers. The point-to-point connection of PanelView 1000 terminals can be established with PLC, SLC, and ControlLogix.
The user must establish the DH+ link. The DH+ link can be connected in two ways:
- Drop line or trunk line
- Daisy chain
Users must consider the following before establishing the DH+ communication link:
- The maximum length of the trunk line cable should not exceed 3048 meters.
- The maximum length of the drop line cable should not exceed 30.4 meters.
- The maximum number of stations connected to a single DH+ link should not exceed 64.
1771 Remote I/O:
The PanelView 1000 terminals with remote I/O ports usually have their catalog number end with a 1. There is a remote I/O port, along with an RS-232 port. The remote I/O terminal provides users with an option for discrete and block data transfer. Users can adopt this configuration by connecting the remote I/O with a PLC or SLC controller, as well as a ControlLogix system on a 1771 remote I/O network.
The information below shows the details of the controllers and scanners compatible with remote I/O terminals:
-
Controller: PLC-5/11, PLC-5/15, PLC-5/20, PLC-5/25, PLC 5-30, PLC-5/60, PLC-5/80, PLC-5/250
- Scanner: PLC Integral 1771-SN
-
Controller: PLC-5/10, PLC-5/12
- Scanner: 1771-SN
-
Controller: PLC-2
- Scanner: 1771-SN or 1772 SD2
-
Controller: PLC-3, PLC-3/10
- Scanner: None for PLC-3, Remote I/O scanner for PLC-3/10
-
Controller: ControlLogix
- Scanner: 1756 DHRIO
-
Controller: VME
- Scanner: 6008 SV
-
Controller: IBM PC
- Scanner: 6008 SI
-
Controller: DC Q-BUS
- Scanner: 6008 SQ
-
Controller: SLC-5/2, SLC-5/3, SLC-5/4, SLC-5/5
- Scanner: 1747-SN
Users can refer to the information above for the selection of the controller and scanner type for their system.
DH-485 Communication:
The PanelView 1000 terminals with DH-485 ports usually have their catalog number ending with 2. There are two ports but PanelView 1000 terminals with a catalog number ending with 3 have 2 DH-845 ports and one RS-232 port for connecting to a printer.
The user can select this PanelView 1000 variant if they want to connect a single SLC or multiple SLCs. For establishing a connection, users can refer to the cables below:
- 1747-C11: 0.3 meters long
- 1747-C10: 1.83 meters long
- 1747-C20: 6.1 meters long
Users can connect multiple SLCs. As there is no electrical isolation between two DH-845 connectors, the user can use a link coupler for establishing electrical isolation.
Users can even establish a connection with a computer. In this case, the user can select any of these cables:
- 1747-C11: 0.3 meters long
- 1747-C10: 1.83 meters long
- 1747-C20: 6.1 meters long
RS-232
PanelView 1000 terminals with a single RS-232 port usually have their catalog number ending with 5. Additionally, PanelView 1000 terminals with a catalog number ending with 9 have one RS-232 communication port and one RS-232 printer port for connecting to a printer. The controllers compatible with an RS-232 port include:
- MicroLogix 1000 controller
- MicroLogix 1200 controller
- MicroLogix 1500 controller
- ControlLogix controller
- CompactLogix controller
- FlexLogix controller
- SLC-/03
- SLC-/04
- SLC-/05
- PLC-/12
- PLC-/15
- PLC-/25
- Enhanced PLC controllers e.g., PLC-5/20E
If users want to connect a PanelView 1000 terminal with an SLC, MicroLogix, or CompactLogix controller, any of the following cables can be used:
- 2711 NC-13: 5 meters long
- 2711 NC-14: 10 meters long
- 2706 NC-13: 3 meters long
The user can also connect PanelView 1000 terminals with MicroLogix controllers using a Link coupler. This will aid in the electrical isolation of a MicroLogix controller.
Working Environment
The working environment for PanelView 1000 terminals is well defined so that the products operate in non-hazardous, as well as hazardous, environments smoothly. The details for working environment parameters are as follows:
- The PanelView 1000C and PanelView 1000G terminals work best within a temperature range of 0 to 55 degrees Celsius (32 to 131 degrees Fahrenheit).
- The storage temperature for both PanelView 1000C and PanelView 1000G terminals ranges from -25 to 70 degrees Celsius (-13 to 158 degrees Fahrenheit).
- The relative humidity range for both PanelView 1000C and PanelView 1000G terminals is 0 to 95% at 0 to 55 degrees Celsius.
- The operating shock for both PanelView 1000C and PanelView 1000G terminals is 15 g.
- The non-operating shock for both PanelView 1000C and PanelView 1000G terminals is 30 g.
- The operating vibration for both PanelView 1000C and PanelView 1000G terminals is 2 g at a maximum frequency of 2000 Hz.